I encountered a similar (maybe) mystery recently: 40A circuit tripping regularly with consistent 24A load. Video of the trip event revealed ONE FRAME with 90A (?!) indicated. More poking around revealed arcing at the wire/breaker interface. Loose wire clamp. Tightening fixed it. Good luck!
Dec 23, 2024, 8:33 PM
{ "uri": "at://did:plc:c5ccp36prfwyangvp2e62oob/app.bsky.feed.post/3ldyrnrqxak2n", "cid": "bafyreifesgkc2bkq4dsmqvlwib7fhbsetnqwwpjxe27a6mt5emywsyl2vy", "value": { "text": "I encountered a similar (maybe) mystery recently: 40A circuit tripping regularly with consistent 24A load.\n\nVideo of the trip event revealed ONE FRAME with 90A (?!) indicated.\n\nMore poking around revealed arcing at the wire/breaker interface.\n\nLoose wire clamp. Tightening fixed it.\n\nGood luck!", "$type": "app.bsky.feed.post", "langs": [ "en" ], "reply": { "root": { "cid": "bafyreid3agu6qau4jbxt6xo27h4vuljppvgwnq37ulmsj7ak4wcueweypa", "uri": "at://did:plc:prelcvfmkts3nqltcmgi6mkw/app.bsky.feed.post/3ldyq6didac25" }, "parent": { "cid": "bafyreid3agu6qau4jbxt6xo27h4vuljppvgwnq37ulmsj7ak4wcueweypa", "uri": "at://did:plc:prelcvfmkts3nqltcmgi6mkw/app.bsky.feed.post/3ldyq6didac25" } }, "createdAt": "2024-12-23T20:33:07.619Z" } }