I encountered a similar (maybe) mystery recently: 40A circuit tripping regularly with consistent 24A load. Video of the trip event revealed ONE FRAME with 90A (?!) indicated. More poking around revealed arcing at the wire/breaker interface. Loose wire clamp. Tightening fixed it. Good luck!

Dec 23, 2024, 8:33 PM

Record data

{
  "uri": "at://did:plc:c5ccp36prfwyangvp2e62oob/app.bsky.feed.post/3ldyrnrqxak2n",
  "cid": "bafyreifesgkc2bkq4dsmqvlwib7fhbsetnqwwpjxe27a6mt5emywsyl2vy",
  "value": {
    "text": "I encountered a similar (maybe) mystery recently: 40A circuit tripping regularly with consistent 24A load.\n\nVideo of the trip event revealed ONE FRAME with 90A (?!) indicated.\n\nMore poking around revealed arcing at the wire/breaker interface.\n\nLoose wire clamp. Tightening fixed it.\n\nGood luck!",